Refrigerants are poured into special reservoirs (ballons, tanks, etc.), made of steel. However, at present a number of manufacturers supply their products in reservoirs made of aluminum. Such reservoirs (ballons) are highly competitive with the steel ones as to their strength, they have smaller mass and are convenient while performing service works. They are used for prepackaging of small portions of a refrigerant. Characteristics of some steel reservoirs fr pure refrigerants and norms of their filling are given in the table.

Characteristics of steel reservoirs for pure refrigerants, according to "Primagaz" company
Reservoir mass, kg Tankage, l Reservoir dimensions (diameter х height), мм Refrigerant kind Refrigerant mass, kg Note
Sold container
0,18 1 80х270 R12
R22
R502
1
1
1
Using of the corresponding valve with output screw fitting 1/4"
4,4 6,2 204x315 R12
R22
R500
7
8
9
The same
16 6,7 138,7x775 R13
R503
6
6
Simple valve with flat bush on output
Reversing containe
9 12 304х348 R12
R22
R500
R502
12
12
12
12
Connection with flat bush
13 26,5 304х562 R12
R22
R500
R502
30
25
25
25
 
28,5 61 34x1134 R12
R22
R500
R502
70
62
57
64
Valve is equipped with two outputs: for liquid and vapor
37 88 34x1535 R12
R22
R502
100
90
95
The same
500 860 (The tank) 800x2213 R12
R22
R502
989
886
903
Output: conical or cylindrical pipe thread трубная резьба (1")

 

Pure refrigerants are those which were not used after their manufacturing, and the refrigerants released after recovery. Impure refrigerants are considered to be those ones which have been derived from the refrigeration facility. Reservoirs designed for drainage of the refrigerants being subject to recovery, are painted in green fluorescing color. Reservoirs for not used or recovered refrigerants are painted in different colors depending on the mark of a refrigerant.

R12 Pale gray R401A Coral red
R22 Bright green R401B Light gray-green
R134a Pale blue R401C Blue-green (aquamarine)
R142b Pink and others    

 

For maintenance of small refrigeration facilities, "Du Pont" company supply packaged into ballons refrigerants of HCFC and HFC groups.

Refrigerant R22 R401A R134a R402A R404A R407C
Refrigerant mass, kg 13,5 12; 13,4 13,6 12,2 9,8 11,6

 

Ballons are delivered vacuumized from the suppliers of refrigerants to their customers . The majority of ballons are provided with two valves with standard thread of 1/4 in., at the same time liquid valve is connected with immersion leg reaching maximum level of ballon filling (80 %).

The level of ballon filling should comply with the international and national requirements; it is established depending on the volume occupied by the liquid refrigerant and pressure developing under this temperature.

Reservoirs for refrigerants are tested for strength. In the table there are given minimal values of pressures of ballon tests for different refrigerants, as well as maximally permissible filling levels.

Minimal pressures of ballon tests for storage of refrigerants, as well as maximally permissible norms of charging according to RTMD norms (Rules of transportation of dangerous cargoes) and ADR (European agreement about international rules of transportation of dangerous cargoes on the roads)*
Refrigerant RTMD ADR
Minimal testing pressure, МPа Maximally permissible level of filling, kg/l Minimal testing pressure, МPа Maximally permissible level of filling, kg/l
R12 1,7 1,17 1,8 1,15
R12B1 1,0 1,64 1,0 1,61
R13 12,0 0,95 10,0 0,83
25,0 1,10 25,0 1,10
R13B1 4,2 1,13 4,2 1,13
12,0 1,50 25,0 1,60
R22 2,9 1,05 2,9 1,03
R23 6,0 0,35 19,0 0,87
25,0 0,95 25,0 0,95
R114 1,0 1,32 1,0 1,30
R115 2,4 1,10 2,5 1,06
R124 1,2 1,20 1,2 1,20
R125 4,0 0,95 3,6 0,95
R134a 2,2 1,04 2,2 1,04
R142b 1,0 0,99 1,0 0,99
R152a 1,7 0,80 1,8 0,79
R500 2,2 1,02 2,2 1,02
R502 3,0 1,05 3,1 1,05
R503 25,0 0,90 10,0 0,66

* Extraction from standard NF E29-795, November 1992.

All the vessels (reservoirs) should be marked and be provided with a table indicating the type of a refrigerant, which can be stored there, mass of a unfilled vessel, volume (charging according to water), testing pressure, legal name of the enterprise and should have the stamp of the State local technical supervision service.

refrigerants
  7.5-INCH
CYLINDER
9-INCH
CYLINDER
9.5-INCH
CYLINDER
12-INCH
CYLINDER
REFRIGERANTS R12, R-22, R-502, R-134a R-11, R12, R-114 R-22, R-500, R-502, R-134a, 404A R-12, R-22, R-500, R-502, R-134a, 404A
REFRIG.FILL WT. 15 lb.(6.8 kg) 30 lb.(13.56 kg) 30 lb.(13.56 kg) 50 lb.(22.7 kg)
WATER CAPACITY 15.8 lb.(7.2 kg) 26.6 lb.(12.0 kg) 29.7 lb.(13.4 kg) 49.6 lb.(22.5 kg)
CYLINDER VOLUME 437 cu.in.(7.2 liters) 737 cu.in.(12.0 liters) 822 cu.in (13.4 liters) 1374 cu.in.(22.5 liters)

 

Mass of the unfilled vessel is considered to be mass of a proper vessel and accessories attached to it without a valve. While indicating this mass on the marking table, they stamp letter M before the figures indicating the mass. Mass of a container is considered to be mass of an unfilled vessel, mass of accessories attached to it and the valve provided with immersion leg. While indicating of this mass on the marking table, its value is preceded by letter T.

In the table there are given as an example technical conditions during the sale of some refrigerants delivered in reservoirs. Often technical conditions are much stricter than it is actually necessary for normal enough operation of the refrigeration facility.

Technical conditions during the sale of some refrigerants (according to "Dehon" company)
Technical conditions during the sale R22 R23 R134a R142b
Maximum mass proportion of moisture, mln-1 10 25 10 10
Maximum volume fraction of noncondensable liquids (in gas phase), % 1,5 1,5 1,5 1,5
Maximum deviation of normal boiling point, oС 0,5 0,5 0,3 0,5
Соntent of НСl Not allowed
Pureness, % 99,8 99 99,7 99,8